Project overview
Project details
- Client
- International design consortium, for a public university client
- Year
- 2025
- Category
- District Cooling
- Location
- Kuwait (health sciences campus)
- ASME B31.1
- AISC 360-16
- ACI 318-14
- CAESAR II
- SAP2000
- IDEA StatiCa
- Support Design
- Closed Loop
Final design of a DN 900 closed-loop chilled water network at a health sciences campus in Kuwait. The scope covers CAESAR II stress analysis, support and base connection design, marked-up layouts and construction drafting.
- DN 900closed-loop network
- 77.0%governing expansion, of allowable
- 14added anchors
The challenge
- The package was inherited mid-stream with the original client submission date unchanged.
- The DN 900 supply and return loop was already built, so the route was frozen: no re-routing, no added expansion loops and no meaningful geometry change.
- A 4.5 °C supply line installed against a 45 °C ambient gives a 40.5 °C contraction, and a closed loop of this size has no free end to absorb it.
- Every fix had to fit the as-built envelope, using bellows, anchors and support detailing only.
Our approach
- The entire loop was modelled as one continuous CAESAR II system, so closure and load paths were solved once instead of being assumed at artificial boundaries.
- Sliding restraints were modelled as unrestrained with steel-on-steel friction at μ = 0.30, conservative for anchor loads and realistic for movement.
- Eight load cases: hydrotest, operating at design and operating pressure, matching sustained pairs, and three expansion combinations including the supply-to-return differential.
- Two untied expansion joints, one per line, relieve axial force. Each has an axial stiffness of 7,700 N/cm, a transverse stiffness of 11,450 N/cm, an angular stiffness of 15,510 N·m/deg and an effective diameter of 955.7 mm.
- Fourteen additional anchors divide the loop into controlled thermal blocks and stop movement from propagating around the ring.
- Revised loads were fed back and every support type was re-verified. Support and anchor reactions were grouped into ten standard support types.
- SAP2000 frame models designed the steel supports to AISC 360-16. IDEA StatiCa Connection models checked base plates, welds, cast-in anchors, concrete blocks and bearing to ACI 318-14.
- Marked-up plan drawings show node numbers, support type callouts, anchor locations, expansion joint positions, tie-in points and contractor scope limits.
The outcome
- Code compliance. Qualified in full against ASME B31.1 with no violations.
- Expansion. The governing case reached 77.0% of allowable, under the 90% ceiling. The second expansion case reached 75.1% and the differential case 11.2%.
- Sustained and hydrotest. Sustained stress peaked at 49.6% at design pressure and 41.4% at operating pressure. Hydrotest reached 24.3%.
- Movement. Thermal excursions of about 147 mm horizontally and 30 mm vertically were absorbed by the bellows-and-anchor arrangement instead of the pipe. Sustained sag was 7.3 mm.
- Supports. All support types passed structurally, with an AISC 360-16 P-M interaction peak of 0.82. Base connections reached 89.0% for anchors, 85.0% for welds and 33.4% for concrete blocks, with plate plastic strain of 1.2% against a 5% limit.
- Reactions. Peak design reactions per support point were 397 kN vertical, 112 kN axial and 95 kN lateral. The governing anchor carried 973 kN axial and 356 kN moment.
- Delivery. The complete package (analysis, support designs, base connections, markups and drafting) was issued within the client's specified duration, covering the gap left by a departing subcontractor and holding the design submission date.
Codes, standards and tools
- ASME B31.1 (2020)
- AISC 360-16
- AISC LRFD 2016
- ACI 318-14 Chapter 17
- UBC 97
- CAESAR II v13
- SAP2000 v20.1
- IDEA StatiCa Connection
- AutoCAD