ISO 14692 stress analysis of a plant-wide buried glass-reinforced epoxy (GRE) firewater network for a new onshore gas treatment plant. It covers 174 lines from 2 to 18 inches, solved in one CAESAR II model, with local laminate reinforcement issued for construction.
- 174lines in one model
- 94.8%governing utilisation
- 153reinforcement entries
The challenge
- GRE cannot be qualified by analogy with steel. The laminate is strongly anisotropic: short-term hoop strength is about 250 MPa, short-term axial strength is 65 MPa, and the axial tensile modulus is roughly half the hoop value.
- A buried, fully restrained pipe under internal pressure and a 54 °C installation-to-operating temperature swing places its main demand on the weak axial direction.
- The coefficient of thermal expansion is 20 × 10⁻⁶/°C, higher than carbon steel, so the restrained thermal load is larger while the available modulus is smaller.
- The joints add complexity. The system is adhesive-bonded taper-bell, not welded, and tees and elbows are moulded or filament-wound components, each with its own qualified envelope that a stress intensification factor does not cover.
- Qualification must use the ISO 14692 biaxial envelope at each component, at design life and temperature, with part factors applied. That differs from a B31.3 code stress ratio.
- The network was analysed as one system: 174 lines from 2 to 18 inches, buried 0.5 to nearly 4 metres deep. On a closed ring main, splitting it into sub-models would change the result.
Our approach
- Built as a single CAESAR II V13 model and solved in one run.
- Each line used a soil model matching its actual cover. Fourteen soil models were defined in 250 mm depth bands from 500 mm to 3,750 mm.
- Material data came from the manufacturer's laminate data, entered as a full orthotropic definition: hoop and axial tensile and bending moduli, shear modulus, volumetric modulus and both Poisson ratios.
- The long-term envelope used qualified stresses at five biaxial ratios: 0:1, 1:1, 2:1, 1:0 and 0:−1. ISO 14692 part factors were applied by load category, with a 0.85 fluid thermal derating factor.
- A 21-case load matrix separated two operating thermal states, resolved expansion as three pairwise combinations, and applied 0.2 g seismic in four horizontal directions, both alone and superimposed on sustained loads. Wind was excluded, since the system is fully buried.
- Local fixes were used where the envelope was exceeded: 18-inch tee bodies increased from 15.4 mm to 23 mm, 500 mm of pipe on each side of those tees from 10.1 mm to 17.7 mm, and 18-inch elbows from 12.4 mm to 18.4 mm, with equivalent local increases at 8, 6, 4 and 2 inches.
- Each increase was recorded in a numbered schedule and marked on the isometric.
The outcome
- With local reinforcement, the network passed all 21 load cases with no code violations.
- Governing utilisation was 94.8% on the operating case at maximum design temperature (42.1 MPa against a 44.4 MPa allowable). Hydrotest reached 76.9%, sustained 69.6%, the second operating thermal state 87.7% and seismic plus sustained (occasional) 54.6%.
- The four operating-plus-seismic cases matched the operating case ratio exactly. The thermal and pressure state governed, not seismic inertia, so the seismic scope was closed.
- Two thrust blocks for the entire plant, both on 18-inch headers, with maximum design loads of 246 kN and 235 kN. A thrust block from an earlier revision was deleted after depth-specific soil restraint showed sufficient friction. Elsewhere, soil friction resists pressure thrust.
- Deliverables: 153 local reinforcement entries across 80 marked-up isometrics. Each entry lists component type, size, original, added and final thickness, and location.
- No pressure class change, re-routing or added anchor blocks were needed, and most of the network was built at catalogue thickness. Issued for construction at Rev. 02.
Codes, standards and tools
- ISO 14692-2017
- ASME B31.3
- ASTM D2310
- ASTM D3567
- ASTM D1599
- ASTM D4024
- ASME B16.5
- API 609
- CAESAR II V13 Basic Soil Model